This module exploits a series of vulnerabilities to achieve unauthenticated remote code execution on the Rockwell FactoryTalk View SE SCADA product as the IIS user. The attack relies on the chaining of five separate vulnerabilities. The first vulnerability is an unauthenticated project copy request, the second is a directory traversal, and the third is a race condition. In order to achieve full remote code execution on all targets, two information leak vulnerabilities are also abused. This exploit was used by the Flashback team (Pedro Ribeiro + Radek Domanski) in Pwn2Own Miami 2020 to win the EWS category.
Exploit database
Vulnerability
CVE-2020-12028
Rockwell Automation FactoryTalk View SE
Vulnerability details
- Score
- 7.3
- Severity
- high
CVSS 3.1 · icscert
Vector string
CVSS:3.1/AV:N/AC:L/PR:L/UI:R/S:U/C:H/I:H/A:NDescription
In all versions of FactoryTalk View SEA remote, an authenticated attacker may be able to utilize certain handlers to interact with the data on the remote endpoint since those handlers do not enforce appropriate permissions. Rockwell Automation recommends enabling built in security features found within FactoryTalk View SE. Users should follow guidance found in knowledge base articles 109056 and 1126943 to set up IPSec and/or HTTPs.
CVE ProgramShowing saved CVE details. Refresh is temporarily unavailable.
Exploit source choices
1 sourceRockwell FactoryTalk View SE SCADA Unauthenticated Remote Code Execution
2020-06-22rockwell_factorytalk_rce.rb