This module exploits a Java deserialization vulnerability in the Inductive Automation Ignition SCADA product, versions 8.0.0 to (and including) 8.0.7. This exploit was tested on versions 8.0.0 and 8.0.7 on both Linux and Windows. The default configuration is exploitable by an unauthenticated attacker, which can achieve remote code execution as SYSTEM on a Windows installation and root on Linux. The vulnerability was discovered and exploited at Pwn2Own Miami 2020 by the Flashback team (Pedro Ribeiro + Radek Domanski).
Exploit database
Vulnerability
CVE-2020-10644
Vulnerability details
- Score
- 7.5
- Severity
- high
CVSS 3.1 · NVD
Vector string
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:NDescription
The affected product lacks proper validation of user-supplied data, which can result in deserialization of untrusted data on the Ignition 8 Gateway (versions prior to 8.0.10) and Ignition 7 Gateway (versions prior to 7.9.14), allowing an attacker to obtain sensitive information.
CVE ProgramShowing saved CVE details. Refresh is temporarily unavailable.
Exploit source choices
1 sourceInductive Automation Ignition Remote Code Execution
2020-06-11inductive_ignition_rce.rb